Secondary Aluminum URD Cable

Secondary Aluminum URD Cable

Votage: 600V

Conductors: Class B compressed concentric lay stranded 1350 aluminum alloy per ASTM B231 or AA-8000 aluminum alloy per ASTM B800 & B801.

Insulation: Phase conductors in black thermoset cross-linked polyethylene (XLPE).  Neutral conductor in black thermoset cross-linked polyethylene (XLPE) identified by yellow striping or full yellow jacket.


0.00
0.00
  

Votage: 600V

Conductors: Class B compressed concentric lay stranded 1350 aluminum alloy per ASTM B231 or AA-8000 aluminum alloy per ASTM B800 & B801.

Insulation: Phase conductors in black thermoset cross-linked polyethylene (XLPE).  Neutral conductor in black thermoset cross-linked polyethylene (XLPE) identified by yellow striping or full yellow jacket.


Overview

Application

The wire is rated at 600V for underground secondary distribution not exceeding 90˚C. It may be directly buried in earth or installed in duct in both wet or dry locations. 

Configuration

Black phase insulated conductors cabled with neutral. Neutral will be marked with yellow striping or yellow jacket.


Construction

Conductors: Class B compressed concentric lay stranded 1350 aluminum alloy per ASTM B231 or AA-8000 aluminum alloy per ASTM B800 & B801.

Insulation: Phase conductors in black thermoset cross-linked polyethylene (XLPE).  Neutral conductor in black thermoset cross-linked polyethylene (XLPE) identified by yellow striping or full yellow jacket.

Features

Individual cables are UL Listed as USE-2

RUS accepted        

Temperature rating of 90˚C dry, wet, and direct burial

Heat, ozone, oil, and chemical resistant

Tear and abrasion resistant


Standards

ICEA S-105-692: 600V Single layer thermoset insulated utility underground distribution cable

UL854:  Service Entrance Cables

RUS accepted

Parameter

Single 600V SECONDARY URD


Code Name

Size

Stranding

Insulation Thickness

Nominal Diameter

Approx. Net Weight

Ampacity NEC1

Ampacity ICEA*

Inches

mm

Inches

mm

lb / kft.

kg/km

60°C

75°C

90°C

Direct Buried2

Pole Riser Conduit3

SINGLE CONDUCTOR 600V SECONDARY URD

Cornell

8

7

0.06

1.52

0.26

6.6

34

51

40

44

49

74

36

Princeton

6

7

0.06

1.52

0.3

7.6

47

70

46

56

59

96

47

Mercer

4

7

0.06

1.52

0.35

8.9

67

100

63

72

81

117

60

Clemson

2

7

0.06

1.52

0.41

10.4

97

144

86

100

108

154

82

Kenyon

1

19

0.08

2.03

0.49

12.4

128

190

98

111

124

171

97

Harvard

1/0

19

0.08

2.03

0.52

13.2

154

229

115

133

146

193

112

Yale

2/0

19

0.08

2.03

0.57

14.5

186

277

132

150

162

221

132

Tufts

3/0

19

0.08

2.03

0.62

15.7

225

335

150

172

189

253

155

Beloit

4/0

19

0.08

2.03

0.68

17.3

274

408

173

200

221

290

185

Hofstra

250

37

0.095

2.41

0.75

19.1

329

490

196

228

248

317

199

Gonzaga

300

37

0.095

2.41

0.81

20.6

385

573

224

255

281

349

223

Rutgers

350

37

0.095

2.41

0.85

21.6

439

653

242

278

302

381

248

Dartmouth

400

37

0.095

2.41

0.9

22.9

493

734

259

300

329

410

272

Brown

450

37

0.095

2.41

0.94

23.9

547

814

---

---

---

439

295

Emory

500

37

0.095

2.41

0.98

24.9

601

894

299

344

378

464

318

Duke

600

61

0.11

2.79

1.09

27.7

725

1079

328

377

416

514

355

Furman

700

61

0.11

2.79

1.16

29.5

830

1235

362

416

459

549

386

Sewanee

750

61

0.11

2.79

1.19

30.2

883

1314

368

427

470

567

403

Fordham

1000

61

0.11

2.79

1.34

34

1144

1702

431

494

540

665

492


DUPLEX TRIPLEX QUADRUPLEX 600V SECONDARY URD

Code Name

Phase Conductor

Neutral

Diameter (mils.)

Weight/kft. (lbs.)

Allowable Ampacities*

AWG

Stranding

Insulation 

Thickness

AWG

Stranding

Insulation 

Thickness

Single Phase

 Cond.

Complete 

Cable


Direct Burial

In Ducts

DUPLEX 600V SECONDARY URD

Bard

8

7

60

8

7

60

262

524

76

70

55

Clafin

6

7

60

6

7

60

298

596

91

95

70

Delgado

4

7

60

4

7

60

345

690

129

125

90

Everett

2

7

60

2

7

60

403

806

189

187

100

TRIPLEX 600V SECONDARY URD

Erskine

6

7

60

6

7

60

298

644

136

95

70

Vassar

4

7

60

4

7

60

345

745

194

125

90

Stephens

2

7

60

4

7

60

403

870

260

165

120

Ramapo

2

7

60

2

7

60

403

870

290

165

120

Brenau

1/0

19

80

2

7

60

512

1106

409

215

160

Bergen

1/0

19

80

1/0

19

80

512

1106

476

215

160

Converse

2/0

19

80

1

19

80

555

1199

490

245

180

Hunter

2/0

19

80

2/0

19

80

555

1199

540

245

180

Hollins

3/0

19

80

1/0

19

80

603

1302

586

280

205

Sweetbriar

4/0

19

80

2/0

19

80

658

1421

740

315

240

Monmouth

4/0

19

80

4/0

19

80

658

1421

847

315

240

Pratt

250

37

95

3/0

19

80

732

1581

857

345

265

Wesleyan

350

37

95

4/0

19

80

831

1795

1135

415

320

Rider

500

37

95

350

37

95

980

2117

1248

495

395

Fairfield

750

61

110

500

37

95

1188

2860

2304

615

525

QUADRUPLEX 600V SECONDARY URD

Tulsa

4

7

60

4

7

60

345

833

258

120

85

Dyke

2

7

60

4

7

60

403

973

367

155

115

Wittenberg

2

7

60

2

7

60

403

973

375

155

115

Notre Dame

1/0

19

80

2

7

60

512

1236

574

200

150

Purdue

1/0

19

80

1/0

19

80

512

1236

596

200

150

Syracuse

2/0

19

80

1

19

80

555

1340

664

225

170

Lafayette

2/0

19

80

2/0

19

80

555

1340

720

225

170

Swarthmore

3/0

19

80

1/0

19

80

603

1456

805

250

195

Davidson

3/0

19

80

3/0

19

80

603

1456

874

250

195

Wake Forest

4/0

19

80

2/0

19

80

658

1588

1036

290

225

Earlham

4/0

19

80

4/0

19

80

658

1588

1066

290

225

Rust

250

37

95

3/0

19

80

760

1830

1213

325

210

Slippery Rock

350

37

95

4/0

19

80

831

1945

1544

385

305

Wofford

500

37

95

350

37

95

990

2390

2251

467

420

Windham

750

61

110

500

37

95

1200

2890

3266

615

492