+86-18945687276
Features:
High Current carrying capacity
Stable at elevated temperatures
Good mechanical properties
Economic design
Best suited for enhancing the existing line capacity where additional power corridors are not feasible.
Features:
High Current carrying capacity
Stable at elevated temperatures
Good mechanical properties
Economic design
Best suited for enhancing the existing line capacity where additional power corridors are not feasible.
Application:
TACSR Conductors are very similar in construction to a conventional ACSR conductor but the EC Grade Aluminum wires are replaced with Hard Drawn Aluminum wires of Heat Resistant Aluminum Alloy (generally known as TAL ) . TACSR can be safely operated continuously above 150oC enabling to pump more current through the conductor. Where there is a need to transmit higher power but restrictions on getting new power corridors approved, various Types of TAL conductors are one of the best creative solution options to utilities. Ability of the Zirconium doped aluminum alloy to maintain its electrical and mechanical properties at elevated temperatures makes these conductors a very cost effective solution in refurbishing the existing lines with enhanced capacity.
TACSR (/AW) is used for overhead electric power transmission lines. Big city, seaside TACSR TACSR/AW CONDUCTOR district, moisture area etc.
Standard:
IEC, ASTM, JEC 3406
Construction:
Core(St, AW): Zinc-coated Steel Wire / Aluminum-clad Steel Wire(AW) : 14% ~ 40% AW
Conductor(TAI) : Thermal Resistant Aluminum HIGH TEMPERATURE CONDUCTOR Alloy Wire used for continuously allowable temperature up to 150oC
Characteristics
AW Type has excellent rustless characteristics.
Thermal-resistant Aluminum Alloy Conductors Steel Reinforced used in the 35KV 110KV 220KV 330KV 500KV 750KV 1000KV substation project, the wire alloying, improve high-temperature performance products, wire section, increase the carrying capacity, high temperature resistance, high conductivity, low loss, reduce power loss, improve the safety of equipment operation. Installation and maintenance are the same as ordinary Aluminum Conductors Steel Reinforced installation procedures, without any special tools, installation, installation, convenient maintenance and low cost.
Conductor Size (mm2) | Stranding (Nos./mm) | Min. Breaking Load (kgf) | Reference | |||||||||||||
Cross-sectional Area (mm2) | Overall Diameter (mm) | Weight (kg/km) | DC Resistance at 20℃ (Ω/km) | Modulus of Elasticity (kgf/mm2) | Coefficient of Linear Expansion (10-6/℃) | Standard Length (m) | Current Carrying Capacity (A) | |||||||||
TAl | ST | TAl | ST | Total | TAl | ST | TAl | ST | Total | |||||||
58 | 6/3.5 | 1/3.5 | 1,980 | 57.73 | 9.621 | 67.35 | 10.5 | 3.5 | 158.1 | 75.04 | 233.1 | 0.505 | 8,400 | 18.9 | 1,000 | 343 |
80 | 6/4.2 | 1/4.2 | 2,770 | 83.10 | 13.85 | 96.95 | 12.6 | 4.2 | 227.5 | 108.0 | 335.5 | 0.350 | 8,400 | 18.9 | 1,000 | 430 |
95 | 6/4.5 | 1/4.5 | 3,810 | 95.40 | 15.90 | 111.3 | 13.5 | 4.5 | 261.2 | 124.0 | 385.2 | 0.306 | 8,400 | 18.9 | 1,000 | 478 |
80 | 15/2.6 | 4/2.6 | 4,720 | 79.64 | 21.24 | 100.9 | 13.0 | 7.8 | 219.2 | 166.5 | 385.7 | 0.368 | 9,390 | 17.6 | 2,000 | 448 |
100 | 15/2.9 | 4/2.9 | 5,580 | 99.08 | 26.42 | 125.5 | 14.5 | 8.7 | 272.8 | 207.1 | 479.9 | 0.296 | 9,390 | 17.6 | 2,000 | 517 |
120 | 15/3.2 | 4/3.2 | 5,550 | 120.6 | 32.17 | 152.8 | 16.0 | 9.6 | 332.2 | 252.2 | 584.4 | 0.243 | 9,390 | 17.6 | 2,000 | 590 |
120 | 30/2.3 | 7/2.3 | 5,540 | 124.7 | 29.09 | 153.8 | 16.1 | 6.9 | 345.7 | 228.0 | 573.7 | 0.237 | 9,080 | 18.0 | 2,000 | 598 |
160 | 30/2.6 | 7/2.6 | 6,980 | 159.3 | 37.16 | 196.5 | 18.2 | 7.8 | 441.5 | 291.3 | 732.8 | 0.185 | 9,080 | 18.0 | 2,000 | 706 |
200 | 30/2.9 | 7/2.9 | 8,640 | 198.2 | 46.24 | 244.4 | 20.3 | 8.7 | 549.3 | 362.4 | 911.7 | 0.149 | 9,080 | 18.0 | 2,000 | 816 |
240 | 30/3.2 | 7/3.2 | 10,210 | 241.3 | 56.29 | 297.6 | 22.4 | 9.6 | 668.9 | 441.3 | 1,110 | 0.122 | 9,080 | 18.0 | 2,000 | 932 |
330 | 26/4.0 | 7/3.1 | 10,950 | 326.8 | 52.84 | 379.6 | 25.3 | 9.3 | 905.4 | 414.2 | 1,320 | 0.0904 | 8,360 | 19.0 | 2,000 | 1,128 |
410 | 26/4.5 | 7/3.5 | 13,910 | 413.4 | 67.35 | 480.8 | 28.5 | 10.5 | 1,145 | 527.9 | 1,673 | 0.0714 | 8,360 | 19.0 | 2,000 | 1,322 |
480 | 45/3.7 | 7/2.47 | 11,260 | 483.8 | 33.54 | 517.34 | 29.6 | 7.41 | 1336.1 | 262.9 | 1,599 | 0.0610 | 7,250 | 20.8 | 2,000 | 1,425 |
520 | 54/3.5 | 7/3.5 | 15,600 | 519.5 | 67.35 | 586.9 | 31.5 | 10.5 | 1,441 | 527.9 | 1,969 | 0.0569 | 7,990 | 19.5 | 1,600 | 1,504 |
610 | 54/3.8 | 7/3.8 | 18,350 | 612.4 | 79.38 | 691.8 | 34.2 | 11.4 | 1,698 | 622.2 | 2,320 | 0.0481 | 7,990 | 19.5 | 1,600 | 1,682 |
680 | 54/4.0 | 7/4.0 | 19,810 | 678.8 | 87.99 | 766.8 | 36.0 | 12.0 | 1,882 | 689.8 | 2,572 | 0.0436 | 7,990 | 19.5 | 1,600 | 1,797 |
680 | 45/4.4 | 7/2.9 | 15,580 | 684.5 | 46.24 | 730.7 | 35.1 | 8.7 | 1,898 | 362.4 | 2,260 | 0.0431 | 7,250 | 20.8 | 1,600 | 1,787 |
810 | 45/4.8 | 7/3.2 | 18,480 | 814.5 | 56.29 | 870.8 | 38.4 | 9.6 | 2,259 | 441.3 | 2,700 | 0.0363 | 7,250 | 20.8 | 1,600 | 2,004 |
1,160 | 84/4.2 | 7/4.2 | 27,830 | 1.163 | 96.95 | 1,260 | 46.2 | 12.6 | 3,236 | 759.8 | 3,996 | 0.0254 | 7,430 | 20.5 | 1,200 | 2,573 |
1,520 | 84/4.8 | 7/4.8 | 36,390 | 1.520 | 126.7 | 1,647 | 52.8 | 14.4 | 4,228 | 993.3 | 5,222 | 0.0195 | 7,430 | 20.5 | 1,200 | 3,035 |
Conductor Size (mm2) | Stranding (Nos./mm) | Min. Breaking Load (kgf) | Reference | ||||||||||
Cross-sectional Area (mm2) | Overall Diameter (mm) | Weight (kg/km) | DC Resistance at 20℃ (Ω/km) | Modulus of Elasticity (kgf/mm2) | Coefficient of Linear Expansion (10-6/℃) | Standard Length (m) | Current Carrying Capacity (A) | ||||||
TAl | AW | TAl | AW | TAl | AW | ||||||||
120 | 30/2.3 | 7/2.3 | 5,540 | 124.7 | 29.08 | 16.1 | 6.9 | 536.5 | 0.219 | 8,100 | 19.2 | 2,000 | 624 |
160 | 30/2.6 | 7/2.6 | 6,980 | 159.3 | 37.16 | 18.2 | 7.8 | 685.4 | 0.171 | 8,100 | 19.2 | 2,000 | 734 |
200 | 30/2.9 | 7/2.9 | 8,640 | 198.2 | 46.24 | 20.3 | 8.7 | 852.8 | 0.138 | 8,100 | 19.2 | 2,000 | 847 |
210 | 30/3.2 | 7/3.2 | 10,160 | 241.3 | 56.29 | 22.4 | 9.6 | 1,038 | 0.113 | 8,100 | 19.2 | 2,000 | 968 |
330 | 26/4.0 | 7/3.1 | 11,200 | 326.8 | 52.84 | 25.3 | 9.3 | 1,252 | 0.0856 | 7,620 | 20.0 | 2,000 | 1,159 |
410 | 26/4.5 | 7/3.5 | 14,230 | 413.4 | 67.35 | 28.5 | 10.5 | 1,587 | 0.0676 | 7,630 | 20.0 | 2,000 | 1,358 |
480 | 45/3.7 | 7/2.47 | 11,260 | 483.84 | 33.54 | 29.6 | 7.4 | 1,561 | 0.0595 | 6,910 | 21.5 | 2,000 | 1,437 |
520 | 54/3.5 | 7/3.5 | 15,920 | 519.5 | 67.35 | 31.5 | 10.5 | 1,883 | 0.0544 | 7,390 | 20.4 | 1,600 | 1,537 |
610 | 54/3.8 | 7/3.8 | 18,730 | 612.4 | 79.38 | 34.2 | 11.4 | 2,219 | 0.0461 | 7,330 | 20.4 | 1,600 | 1,717 |
680 | 45/4.4 | 7/2.9 | 15,580 | 684.5 | 46.24 | 35.1 | 8.7 | 2,201 | 0.0422 | 6,900 | 21.5 | 1,600 | 1,805 |
810 | 45/4.8 | 7/3.2 | 18,730 | 814.5 | 56.29 | 38.4 | 9.6 | 2,628 | 0.0354 | 6,910 | 21.5 | 1,600 | 2,028 |
950 | 84/3.8 | 7/3.8 | 23,780 | 952.6 | 79.38 | 41.8 | 11.4 | 3,170 | 0.0302 | 7,030 | 21.2 | 1,200 | 2,292 |
1,160 | 84/4.2 | 7/4.2 | 28,720 | 1,163 | 96.95 | 46.2 | 12.6 | 3,872 | 0.0247 | 7,030 | 21.2 | 1,200 | 2,606 |
1,520 | 84/4.8 | 7/4.8 | 37,520 | 1,520 | 126.7 | 52.8 | 14.4 | 5,060 | 0.0189 | 7,030 | 21.2 | 1,200 | 3,075 |
Conductor Size (mm2) | Stranding (Nos./mm) | Min. Breaking Load (kgf) | Reference | ||||||||||
Cross-Sectional Area (mm2) | Overall Diameter (mm) | Weight (kg/km) | DC Resistance at 20 ( /km) | Modulus of Elasticity (kgf/mm2) | Coefficient of Linear Expansion (10-6/ ) | Standard Length (m) | Current Carrying Capacity (A) | ||||||
TAL | AW | TAL | AW | TAL | AW | ||||||||
120 | 30/2.3 | 7/2.3 | 5,410 | 124.7 | 29.08 | 16.1 | 6.9 | 528.9 | 0.217 | 7,980 | 19.4 | 2,000 | 625 |
160 | 30/2.6 | 7/2.6 | 6,810 | 159.3 | 37.16 | 18.2 | 7.8 | 675.7 | 0.170 | 7,980 | 19.4 | 2,000 | 736 |
200 | 30/2.9 | 7/2.9 | 8,440 | 198.2 | 46.24 | 20.3 | 8.7 | 840.7 | 0.136 | 7,980 | 19.4 | 2,000 | 854 |
210 | 30/3.2 | 7/3.2 | 10,210 | 241.3 | 56.29 | 22.4 | 9.6 | 1,024 | 0.112 | 7,980 | 19.4 | 2,000 | 973 |
330 | 26/4.0 | 7/3.1 | 10,950 | 326.8 | 52.84 | 25.3 | 9.3 | 1,238 | 0.085 | 7,540 | 20.2 | 2,000 | 1,163 |
410 | 26/4.5 | 7/3.5 | 13,910 | 413.4 | 67.35 | 28.5 | 10.5 | 1,570 | 0.0671 | 7,550 | 20.2 | 2,000 | 1,363 |
480 | 45/3.7 | 7/2.47 | 11,110 | 483.84 | 33.54 | 29.6 | 7.4 | 1,550 | 0.0592 | 6,880 | 20.6 | 2,000 | 1,441 |
520 | 54/3.5 | 7/3.5 | 15,600 | 519.5 | 67.35 | 31.5 | 10.5 | 1,865 | 0.0541 | 7,330 | 20.6 | 1,600 | 1,541 |
610 | 54/3.8 | 7/3.8 | 18,350 | 612.4 | 79.38 | 34.2 | 11.4 | 2,198 | 0.0458 | 7,320 | 20.6 | 1,600 | 1,722 |
680 | 45/4.4 | 7/2.9 | 15,600 | 684.5 | 46.24 | 35.1 | 8.7 | 2,189 | 0.0420 | 6,860 | 21.6 | 1,600 | 1,809 |
810 | 45/4.8 | 7/3.2 | 18,480 | 814.5 | 56.29 | 38.4 | 9.6 | 2,613 | 0.0353 | 6,880 | 21.6 | 1,600 | 2,031 |
950 | 84/3.8 | 7/3.8 | 23,100 | 952.6 | 79.38 | 41.8 | 11.4 | 3,149 | 0.0300 | 6,980 | 21.3 | 1,200 | 2,299 |
1,160 | 84/4.2 | 7/4.2 | 28,270 | 1,163 | 96.95 | 46.2 | 12.6 | 3,847 | 0.0246 | 6,980 | 21.3 | 1,200 | 2,611 |
1,520 | 84/4.8 | 7/4.8 | 36,960 | 1,520 | 126.7 | 52.8 | 14.4 | 5,027 | 0.0189 | 6,980 | 21.3 | 1,200 | 3,075 |
Hebei Hualun Cable Co., LTD., founded in November 1985, is the designated manufacturer of the Ministry of Electrical and Mechanical Engineering, is a large key enterprise in North China, the company is located in Hejian Industrial zone, Hebei Province, in the center of Beijing, Tianjin, stone triangle,