Application:
These cables are suitable for MV power applications, particularly for connections in transformer stations and power stations, between aerial lines and transformer stations, and for automotive electric powertrain.
Characteristics
Voltage Rating
12/20 (24kV)
Temperature Rating
Operating temperature: +90ºC
Short Circuit: +250 °C
Minimum Bending Radius
Single core: 13 x overall diameter
During Installation: 26 x overall diameter
Multicore: 6 x overall diameter
During Installation: 12 x overall diameter
Construction
Conductor
Class 2 Aluminium stranded wire
Conductor Screen
Semi-conductive XLPE (Cross-linked Polyethylene) bonded to
conductor
Insulation
XLPE (Cross-linked polyethylene)
Insulation Screen
Grooved peelable semi-conducting XLPE (Cross-linked Polyethylene)
Tightness powder in the grooves
Screen
Al/PET (Aluminium foil tape)
Outer Sheath
PE (Polyethylene)
Standards
IEC 60228, NFC 32-070, NF C 32 013, NF C 33-226, HD 620, UTE C 33-226
Flame retardant NFC 32-070 cat. C2 (grey and black striped outer sheaths only)